Major Fire Incident in an Indian Refinery

Similar documents
ACME Fluid Systems. Strainer Selection Guidelines Web:

INTRODUCTION TO CUSTOM FABRICATED STRAINERS

SIMPLEX STRAINER MODEL 90

Eaton Filtration, LLC

GAS BARBECUE MODEL NO: BBQ4 USER GUIDE PART NO: /11

Strainers In-Line and Angle

Optimal solutions for your success.

HYGIENIC MANAGEMENT OF CELLARS AND CLEANING OF BEER DISPENSE LINES

Eaton Filtration, LLC

Installation & Parts Manual 2" & 3" High Capacity Strainers For Class 1, Petroleum Applications

SPC-60 Service / Training Manual

STAINLESS STEEL GAS BARBECUE MODEL NO: SSBBQ4 USER GUIDE PART NO: /11

JUICE EXTRACTION AND FILTRATION JUICE EXTRACTION METHOD AND EQUIPMENT

Upflow Carbon Installation & Start-Up Guide

EATON DUPLEX BASKET STRAINERS

PARTS DIAGRAMS ESI stocks a complete line of Franke parts. For parts order and inquiries, please contact the ESI parts department at

TITAN S EXPERIENCE IN PHYSICAL SEPARATION DEVICES

Fluid Motion, Part 8. No Strain, No Gain: suction strainer innovations

Thermal Hydraulic Analysis of 49-2 Swimming Pool Reactor with a. Passive Siphon Breaker

Drying, Storing and Handling Dry Edible Bean Ken Hellevang, NDSU Extension Agricultural Engineer

USER MANUAL SSSSSSSSSSSS SSSSSSSSSSSS SSSSSSSSSSSS SSSSSSSSSSSS SSSSSSSSSSSS SSSSSSSSSSSS SSSSSSSSSSSS SSSSSSSSSSSS SSSSSSSSSSSS SSSSSSSSSSSS BSC01

Wega Mininova 2003 Installation Instructions

A very easy charcoal maker Steve McGrew Incandescent Ironworks, Ltd. May 21, 2012

BERTHA Instruction Manual

Read the instructions, keep them safe, pass them on if you pass the appliance on. Remove all packaging before use.

Analyzing & Troubleshooting Plunger Lifted Wells

94306 Vertical Flame Arrester. Features. Vertical Flame Arrester. Unitized tube bank design

Dissolved Oxygen. Management. WineEng Experiences in Brewing and Beer. Experiences in Brewing and Beer by David Medlyn, Coopers Brewery

General. Setup and Placement

2009 Australian & New Zealand Winemakers P/L

OPERATING MANUAL. Sample PRO 100 Series. Electric Heating. Applies to Versions: SPE1*, SPE2, SPE4, SPE6

Smart Plunger TM by PCS

KRONES fillers for wine and sparkling wine Filling of glass containers

COMBUSTIBLE DUST AWARENESS

BOKELA BACKFLUSH FILTER

CMC DUO. Standard version. Table of contens

Jura Impressa XF50. Operating & cleaning Instructions Malvern Road Glen Iris VIC 3146 ph: fax:

Installation and User Instructions Flushing System Kit

TKMSX 1 CAFEMINO ELECTRIC COFFEE ROASTING MACHINE USER MANUAL

INTRODUCTION. Your new smoker comes almost completely assembled. You will need to complete the assembly which includes:

CAUTIONS FOR ALL DEEP FAT FRYERS NEVER LEAVE AN OPERATING FRYER UNATTENDED REMEMBER HOT OIL IS DANGEROUS RESPECT IT! WARNING INSTALLATION Locate your

GAGGIA VALUES LONG ESPRESSO TRADITION AT HOME AS IN COFFEE SHOP EASY MULTIPLE CHOICE

ON-SITE TECHNICAL INFORMATION

Beer Hardware, Systems and Delivery

Design of Conical Strainer and Analysis Using FEA

IMPORTANT SAFEGUARDS. 3. To protect against fire, electric shock and injury to persons do not immerse cord, plug or unit in water or other liquid.

Unsere aktuellste Innovation:

TECHNOLOGIES DEMONSTRATED AT ECHO: BRIQUETTE PRESSES FOR ALTERNATE FUEL USE

Model 48 Resilient Wedge Gate Valve

RG4 AND RG7 INSTALLTION AND MAINTENANCE

TABLE OF CONTENTS HAND MIXER SAFETY

Isomac Tea. A Closer Look. Isomac Tea closer look v6.doc

NZQA registered unit standard version 1 Page 1 of 5

Unit 4P.2: Heat and Temperature

INSTALLATION AND OPERATION MANUAL FOR GAS TILTING BRAISING PANS MODELS G30TB & G40TB

OPERATION & MAINTENANCE MANUAL

TECHNICAL INFORMATION CVA615 Coffee System

Downflow Conversion Kit used to Modify Air Handler Units for Downflow Application

SAFETY INSTRUCTIONS FOR USE

Read the instructions, keep them safe, pass them on if you pass the coffee maker on. Remove all packaging, but keep it in case you ever need to

BC ROASTERS LINEUP. The Commercial Coffee Roasters. BuckeyeCoffee.com

Black Towable Spit. Instructions

Mentos very quickly and in huge quantities and shoot out of the bottle.

Caffeo. Italian style espresso machine. INSTRUCTIONS FOR USE. Breville Customer Service Centre

Appendix 2. Food Safety Plan Worksheets

EGG IN BOTTLE. Next: Materials and Explanations. Then: Step-by-Step Photo Sequence.

BC Gold Standard Lineup!

TKMSX 1 CAFEMINO GAS COFFEE ROASTING MACHINE USER MANUAL

Introduction. No Hassle Guarantee

Make & Taste DAIRY. Lesson Activity. Butter (Grades 3-5) LESSON OVERVIEW: LESSON OBJECTIVES: LESSON MATERIALS NEEDED: ACADEMIC INTEGRATION

C27 Chromatography. Collect: Column Mortar and pestle Dropper (229 mm) Capillary tube TLC plate Aluminum foil UV light

ASSEMBLY & OPERATION INSTRUCTIONS FOR OUTDOOR GAS BARBECUES

BIO Lab 4: Cellular Respiration

Processing of Pasteurized Market Milk

Built in Electric Fan Oven

FIREPLACES - MSRP COST

+ = Power up your Smart Cup while pressing the corresponding button to reach different program modes. Heat Exchange fill/tank Drain Page:

User Guide CQUBE M Espresso

CHOQUENET S.A.S. FOUNDED IN1925

NORTH / 1KG. Mill City Roasters, LLC rd Ave SE Minneapolis, MN 55414

Liquids Handling in Bakeries.

GE Active Containment Sump Strainer for PWR Applications

Clean and sanitize hot sundae topping pumps Weekly SS 1 W3

Organic Chemistry 211 Laboratory Gas Chromatography

SNAP-ON AND STRAP-ON PIPE MARKERS

Eating Soy Free at UMass Amherst

APPLICATION PACK FOR TRADE, CRAFT, FOOD AND CHARITY STALLS WITH TERMS AND CONDITIONS

Contents. Fittings and parts checklist

5 Litre Party Keg Manual

Instruction manual LIVIA G4 DEPID LIVIA G4 PM

SCA Premier Training Campus

RV DN PVC-U. Sediment strainer

Training Guide Hammond Pedestal Grinders

Hotpoint H/A - Ariston automatic, built-in coffee machine MCX 103 X - MCK 103 X/HA

TKMSX 15 COFFEE ROASTING MACHINE

2016 HSC Hospitality Food and Beverage Marking Guidelines

Electric Two-Speed Drink Mixer

ENZX. EBARA Submersible Slurry Pump. Contents Project: Model: Chk d: Date:

USER MANUAL JOLLY PRESTIGE - COFFEE MACHINE

YNV Corperation Vision

Transcription:

Major Fire Incident in an Indian Refinery - V.J.Rao / Tarsem Singh / M.Gupta The Incident: A fire broke out in the month of January, 2016 from the strainer flange of VDU column bottom pump in Atmospheric & Vacuum Distillation Unit (AVU) while carrying out the strainer cleaning job of the pump in an Indian Refinery. There was no injury to any person during the incident. The impact of the fire was felt locally around the source of the hydrocarbon (strainer flange) and damaged some cables, small pipeline sections, a few air fin coolers fans, insulation and cladding. Sequence of events. The general arrangement view of the VDU column bottom to pumps suction is given in Sketch below.

Pump P-25A was isolated at around 09-30 hrs. It was allowed to cool for some time to avoid draining of high temperature vacuum residue (VR) to closed blow down (CBD). In the second shift (starting at 14-00 hrs) the operator started flushing oil (FLO) at the pump suction (downstream of isolation valve) valve to flush the VR. Operator had kept the pump casing drain and the suction strainer flange drain open and after considerable flushing was done, the sample at the OWS point was checked and found that a thin black liquid was coming. Operator shut all the valves including FLO and made ready to be handed over to maintenance. Meanwhile the running pump P-25B started which was making heavy noise. Maintenance advised stopping the pump to check. Accordingly, P-25 C was started and P-25B was stopped. However P-25C was also found cavitating with heavy noise and vibration. The pump was started and stopped several times thinking that lighters are causing the cavitation. Meanwhile P-25A was ready for handover and the permit for opening the strainer was given to maintenance crew. To ensure that pump P-25A is isolated, the crew was asked to open the flange on the strainer drain line downstream of the isolation valve. Since no liquid was observed the alternate bolts of the main strainer flange of 14 inches was opened. Since again no liquid or gas was observed the other bolts were loosened and a gap of about 1 inch between the two flanges was made. Nothing came out immediately. However, some small amount of vapour started coming after a few minutes when maintenance team disturbed the strainer inside using a rod. The amount of vapour coming out increased after another couple of minutes. Within another 1-2 minutes some liquid started pouring down from the bottom of the flange. Immediately the liquid caught fire and the vapour travelling up also caught fire. Firefighting was started with all resources. Fire was put off by around 21-30 hrs. Analysis: There was no oil/ vapour coming out of the strainer drain valve flange when it was opened. This indicates that there was no flow from the strainer to CBD/OWS. When the strainer flange was opened, again nothing came out indicating that no liquid has flown through the small bore drain line.

When the contractor workmen started creating space between the two opened flanges and disturbed the strainer inside, small amount of vapour came out indicating that the strainer disturbance created a path for the liquid to flow. It was found that lot of structured packing material from inside the column was found in the strainer and the same was removed when the strainer was opened after the fire incident. Strenuous material in P 025A suction strainer The isolation valve of P-25A (which was lying outside) was also observed with structured packing between the valve gate and the valve seat restricting the full closure of the valve. It was observed that about 5-8% of the valve remained open due to this structured packing.

Gap between valve gate & seat seen Extraneous (packing) material at the seat area blocked the valve Reconstructed sequence of events: When the pump was isolated and allowed to cool for about 4 hours the VR inside the suction & discharge piping partly got congealed but was not depressurized as the suction valve was passing. When flushing was done and checked at OWS the liquid was coming from pump casing and not strainer flange. This was because the strainer flange was choked with structured packing material and hence did not allow the partially congealed VR to flow out. FLO flowed past the strainer to the casing and got drained from the casing drain. Since the strainer drain flange was kept open during FLO flushing, the operator thought that flushing oil has come out through this strainer drain line also, which was not true as observed.

When the strainer was disturbed by the contractor workmen, the liquid pressure due to the passing suction valve found a way to come out from the open strainer flange. VR started coming out first as vapour and then in large amounts when the congealed VR started de-congealing at the temperature of about 300 deg C and finally the liquid VR came out and started falling down. VR temperature being higher than auto ignition temperature (220 deg C), it caught fire immediately. Although the common remotely operated isolation valve (XZV-3014) on the line was shut by remote PB as well as local push button but it did not function. It was observed (when the valve was opened up after the fire) that the ball valve was stuck at 90% open and hence the complete liquid hold up volume in the column fed to the fire which lasted for more than 3 hours. 90% valve is in open condition XZV 3014 (Shut off valve)

Root Causes of the Fire: The extraneous structured packing material blocking the suction valve and choking the strainer drain flange opening misguided / misled the operations team to believe that the pump was isolated and depressurised. But in reality, it was not depressurised / drained and not positively isolated from the pressurised system. This led to Vacuum Residue (VR) at more than auto-ignition temperature to come out of the suction strainer flange (when it was wedge gapped for opening) and continuously fed the fire that broke out. Major Recommendations: When the VR pumps are isolated, the cooling period should be reviewed so that it does not get congealed and draining with FLO can be ensured. The SOP on this aspect should be reviewed. The isolation valve of the pump was not fully closed as could be seen from the spindle and from the gap in valve gate & seat when the valve was opened. A fool-proof mechanical arrangement to be made (like it is made in all gear operated valves) to ensure that the operator is guided to understand the valve is fully closed or not. When flushing is carried out for any isolated equipment (especially congealing liquids), Job Safety Analysis should consider the chances of congealing or extraneous material choking the drain line and accordingly SOPs for handing over of equipment to be made. The strainer area of each of the VR pumps to be checked with standards (for congealing /choking VR service) and accordingly modified, if required. Before every start-up of the unit the ROV/SOV has to undergo functionality test and recorded. Additional escape route on the strainer platform to be provided near the pump.