Pub #105315revA process networking solutions and Profibus DP (16) DIN Rail Mount Drop Connectors Approval Agency Controlled Document. No Changes Authorized Without Prior Agency Approval 2011 tonel tonel One tonel Dr 26271 U Hwy 59 Fergus Falls, MN 56537 UA Telephone: 218.739.5774 Toll Free: 800.843.7866 Fax: 218.739.5776 Email: sales@stonel.com Website: www.stonel.com
Table of Contents Pub # 105315revA Page 2 Table Of Contents... Page 2 Module Guide... Page 3 General pecifications and Ratings... Page 3 Dimensional Data... Page 3 DR465039_ Modbus/Profibus DP Passive Drop Connector (Bus In/Out and (6) Drops)... Page 4 DR465043_ Modbus/Profibus DP Protected (240mA) Drop Connector (Bus In/Out and (6) Drops)... Page 5 DR465047_ Modbus/Profibus DP witched Protected (240mA) Drop Connector (Bus In/Out and (6) Drops) Page 6 tonel Phone: (218) 7395774 Website: www.stonel.com
DR Pub # 105315revA Model Guide Page 3 Function Brand Options 465039 Modbus/Profibus DP Passive Drop Connector (Bus In/Out and (6) Drops) 465043 Modbus/Profibus DP Protected (240mA) Drop Connector (Bus In/Out and (6) Drops) 465047 Modbus/Profibus DP witched Protected (240mA) Drop Connector (Bus In/Out and (6) Drops) A tonel M Metso ***** (pecial) General pecifications Materials of Construction Operating Life Unlimited Housing Glass Filled Polycarbonate Temperature Range 40 to 80 C (40 to 176 F) Fasteners tainless teel Enclosure Protection IP20 Warranty Two Years Dimensions in inches 35mm 6.5 35mm DIN Rail Clips (Two per unit) 135.40mm centertocenter 3.0 2.20 35mm tonel Phone: (218) 7395774 Tollfree: (800) 8437866 Website: www.stonel.com
Voltage Range Operating Voltage Current Rating Break Current Reset Current DR465039_ pecifications & Wiring Diagrams Modbus and Profibus DP Passive Drop Connector Bus in, Bus out, and (6) Passive Drops for Modbus and Profibus DP networks. 35VDC Modbus Voltage 8 Amps None None Pub #105315revA Page 4 Current Consumption 10mA max Voltage Drop (Trunk) Negligible Voltage Drop (pur) Negligible LED Display: BU POWER, Green LED (Flashing = low voltage) BU BU BU BU B U BU POWER G BU BU Flashing: Low Voltage BU BU DROP 1 BU BU BU BU BU BU DROP 2 BU BU DROP 3 BU BU BU BU BU BU DROP 4 BU BU DROP 5 BU BU BU BU BU BU DROP 6 BU BU tonel Phone: (218) 7395774 Tollfree: (800) 8437866 Website: www.stonel.com
Voltage Range 30 VDC max Operating Voltage DeviceNet Voltage Current Rating 8 Amps (Bus) Break Current >240mA (on )* Holding Current 28mA Reset Current <28mA *hort circuit protection only on. Communication wires are passive DR465043_ pecifications & Wiring Diagrams Modbus and Profibus DP Power Protected Drop Connector Bus in, Bus out, and (6) Power Protected Drops for Modbus and Profibus DP networks Pub #105315revA Page 5 Current Consumption 10mA max Voltage Drop (Trunk) Negligible Voltage Drop (Drop) 1.0 VDC max LED Displays: BU POWER, Green LED (Flashing = low voltage) PWR, Green LED, Drop Energized BU BU BU BU BU POWER G Flashing: Low Voltage DROP 1 BU BU BU BU B U BU BU BU BU DROP 2 BU BU BU BU BU BU DROP 3 BU BU BU BU DROP 4 BU BU BU BU DROP 5 BU BU BU BU DROP 6 BU BU tonel Phone: (218) 7395774 Tollfree: (800) 8437866 Website: www.stonel.com
Pub #105315revA DR465047_ pecifications & Wiring Diagrams Page 6 Modbus and Profibus DP witched Power Protected Drop Connector Bus in, Bus out, and (6) witched Power Protected Drops for Modbus and Profibus DP networks. Voltage Range 30 VDC max Operating Voltage DeviceNet Voltage Current Rating 8 Amps (Bus) Break Current >240mA (on )* Holding Current 28mA Reset Current <28mA *hort circuit protection only on. Communication wires are passive Current Consumption 10mA max Voltage Drop (Trunk) Negligible Voltage Drop (Drop) 1.0 VDC max LED Displays: BU POWER, Green LED (Flashing = low voltage) PWR, Green LED, Drop Energized BU BU BU B BU U BU BU BU POWER G Flashing: Low Voltage BU BU Drop Disconnect witch Operation 1.To energize a selected drop, compress ears of yellow disconnect switch with finger tips and push down. Green PWR LED of selected drop will light. 2. To deenergize a selected drop, compress ears of yellow disconnect switch with finger tips and pull up. Green PWR LED of selected drop will extinguish. Drop is now isolated from the network. BU BU BU BU DROP 1 DROP 3 BU BU BU BU BU BU BU BU G PWR DROP 2 G PWR DROP 4 BU BU BU BU BU BU DROP 5 BU BU BU BU G PWR DROP 6 BU BU tonel Phone: (218) 7395774 Tollfree: (800) 8437866 Website: www.stonel.com